Heat loss calculator

Areas and R-values in, BTU/h out, for one room or the whole house. Conduction is U × A × ΔT, air leakage is 1.08 × CFM × ΔT, and the breakdown shows where the heat goes.

  • Free, no sign-up
  • Runs in your browser
  • Estimate: shows its formulas

What are you calculating?

Scope

Switching loads an example you can edit.

Design temperatures

99% heating and 1% cooling dry bulb, from ASHRAE Handbook—Fundamentals design conditions via Climate.OneBuilding.org. Your local code may set its own values.

°F
°F
ft

Surfaces

U = 1 ÷ R
  • ft²
    R-value
    9,540 BTU/h
  • ft²
    U-factor
    6,110 BTU/h
  • ft²
    R-value
    510 BTU/h
  • ft²
    R-value
    1,670 BTU/h
  • ft²
    R-value
    1,670 BTU/h

Air leakage

ft²
ft
Leakage from
ACH

Volume 16,000 ft³ · 94 CFM of outside air

CFM

Design heat loss

Whole house · estimate

Total heat loss
24,800 BTU/h
7.3 kW · ΔT 63.6°F
Per ft² of floor
12.4
BTU/h·ft²
UA (whole)
390
BTU/h·°F; load at any temp = UA × ΔT

Where the heat goes

  • Walls9,540 · 38%
  • Windows6,110 · 25%
  • Air leakage5,300 · 21%
  • Ceiling / roof1,670 · 7%
  • Floor1,670 · 7%
  • Doors510 · 2%
Check a heat pump against this load

Steady-state conduction plus air leakage. No credit for sun or internal gains, no duct losses, and no below-grade detail.

How to calculate heat loss

Design heat loss is the heat a building loses on a cold day at the outdoor design temperature, with no help from the sun, people or appliances. It is steady-state physics, as set out in the ASHRAE Handbook—Fundamentals, and it comes down to two terms.

Conduction through each surface

Q = U × A × ΔT
U = 1 ÷ R (BTU/h·ft²·°F), A = area (ft²), ΔT = indoor − outdoor design temperature (°F)

Every wall, window, door, ceiling and floor gets its own line. Windows are rated by U-factor already; for insulated assemblies, a whole-assembly R-value (framing included) is more honest than the insulation's label. A slab on grade loses most of its heat at the edge, so it is counted per foot of exposed perimeter with an F-factor instead of per square foot.

Air leakage

Q = 1.08 × CFM × ΔT
1.08 = 0.075 lb/ft³ × 0.24 BTU/lb·°F × 60 min/h at sea level; lower at altitude

CFM is outside air leaking in. From a blower-door test, natural leakage is roughly ACH50 ÷ N (the LBL N-factor, about 10 to 25), and CFM = ACH × volume ÷ 60. The 1.08 factor assumes sea-level air; at altitude the air is thinner and carries less heat per CFM, so the calculator scales it with the standard atmosphere.

A worked example

A 1,000 ft² wall at R-13 with 70°F inside and 0°F outside loses 1 ÷ 13 × 1,000 × 70 ≈ 5,385 BTU/h. 200 ft² of U-0.30 windows add 0.30 × 200 × 70 = 4,200 BTU/h: a fifth of the area, nearly as much heat. That is why windows and air leakage so often top the breakdown.

From heat loss to equipment

A whole-house number is a good start, but equipment and ducts are sized room by room, and a Manual J also counts duct losses, below-grade walls and construction details in a standard way. Take this total to the heat pump balance point calculator, try the quick HVAC load calculator for cooling, or read what a Manual J calculation covers.

Heat loss questions

How do you calculate heat loss?
Add conduction through each surface, U × A × ΔT, where U = 1/R, A is the area in square feet and ΔT is indoor minus outdoor design temperature. Then add air leakage, 1.08 × CFM × ΔT, where CFM is the outside air that leaks in. The total is the design heat loss in BTU/h.
What outdoor temperature should I use?
Use the 99% heating design dry bulb for the nearest representative weather station: the temperature the site is colder than for only about 88 hours in an average year. Building departments may publish their own design temperatures; use theirs if they do.
How do I turn a blower door number into CFM?
Divide ACH50 (or CFM50) by an N-factor of roughly 10 to 25 to estimate natural air leakage. Around 15–20 suits a typical one- or two-story house; use a lower N for tall or exposed houses, where leakage on a cold windy day is higher. For ACH, CFM = ACH × volume ÷ 60.
Why does my R-value give a higher loss than I expected?
Nominal R-values ignore framing. Studs, plates and headers conduct more heat than the cavity insulation, so a 2×4 wall with R-13 batts performs closer to R-10 or R-11 overall. Use whole-assembly U-factors if you have them.
Is heat loss the same as a Manual J heating load?
It is the core of it. A Manual J heating load also accounts for ducts outside the conditioned space, below-grade surfaces, construction details and local conditions in a standard way, room by room, which this calculator does not.